Technical Specification: Access Control and Time Attendance System

This specification covers an IP-based electronic access control system with integrated time attendance, from management software, door controllers, readers and locks to the fire alarm interface, testing and handover. It is written for consultants, engineers and contractors to use in tender documents with light editing.

Vendor-neutral, no brand names. Review it against the code adopted for your project and fill in the values in [brackets].

PART 1 — GENERAL

1.1 Scope of Work

This section covers the supply, installation, programming, testing and commissioning of a complete IP-based Electronic Access Control System (EACS) with integrated Time Attendance for [project name], including:

  • Access control management software, server and licences for [number of doors: 40] controlled doors and [number of cardholders: 1,000], with not less than [20%] spare licence capacity.
  • Networked door controllers, readers, credentials and enrolment readers.
  • Locking hardware (electromagnetic locks, electric strikes, electric mortise locks), exit buttons, emergency break-glass units and door contacts.
  • Power supplies with battery backup for controllers and locks.
  • Interface to the fire detection and alarm system for release of doors on alarm.
  • Time attendance terminals [number of terminals: 4] and time attendance software with reports.
  • Turnstiles or speed gates [optional: number of lanes] and visitor management [optional].
  • All cabling, containment, labelling, training, documentation and warranty.

The Contractor shall coordinate with the door supplier, fire alarm contractor and network contractor.

1.2 Related Sections and Systems

  • Structured cabling system.
  • Data network (LAN switches, PoE, VLANs).
  • Fire detection and alarm system.
  • Video surveillance; doors and ironmongery.
  • Electrical power and UPS.

1.3 Reference Standards

The system shall comply with the latest editions of the following standards, the Egyptian fire protection code and Civil Defence requirements.

StandardTitle
IEC 60839-11-1Alarm and electronic security systems – Part 11-1: Electronic access control systems – System and components requirements
IEC 60839-11-5Alarm and electronic security systems – Part 11-5: Electronic access control systems – Open supervised device protocol (OSDP)
ISO/IEC 14443Identification cards – Contactless integrated circuit cards – Proximity cards
ISO/IEC 7810Identification cards – Physical characteristics
EN 1125Building hardware – Panic exit devices operated by a horizontal bar, for use on escape routes
EN 179Building hardware – Emergency exit devices operated by a lever handle or push pad, for use on escape routes
EN 13637Building hardware – Electrically controlled exit systems for use on escape routes
IEC 62368-1Audio/video, information and communication technology equipment – Part 1: Safety requirements
IEC 60529Degrees of protection provided by enclosures (IP Code)
IEC 62262Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code)
IEC 60331Tests for electric cables under fire conditions – Circuit integrity
IEEE 802.3af/atPower over Ethernet / Power over Ethernet Plus
ANSI/TIA-568.2-DBalanced Twisted-Pair Telecommunications Cabling and Components Standard
ANSI/TIA-606Administration Standard for Telecommunications Infrastructure
ANSI/TIA-607Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
IEC 60332-1, IEC 61034, IEC 60754Flame propagation, smoke density and halogen acid gas tests for cables (LSZH)

Personal data, including biometric data, shall be processed in accordance with the Egyptian personal data protection law.

1.4 Definitions

  • Door controller (ACU): a field panel that stores the database locally and makes access decisions.
  • Credential: card, key fob, PIN or biometric template.
  • Anti-passback: prevents re-entry with the same credential without a recorded exit.
  • Interlock (mantrap): a group of doors of which only one may be open at any time.
  • Fail-safe: a lock that releases when power is removed. Fail-secure: a lock that remains locked when power is removed.
  • REX: request-to-exit device (exit button or sensor).
  • OSDP: Open Supervised Device Protocol, a bidirectional RS-485 reader protocol with encryption (Secure Channel).
  • Wiegand: a legacy unidirectional, unencrypted reader interface.

1.5 Submittals

  • System architecture and riser diagram showing server, network, controllers and doors.
  • Door schedule listing for each door: door number, location, door type, reader type, lock type, fail mode (safe/secure), exit device, fire alarm release group and access level.
  • Shop drawings and typical door wiring diagrams for each door type.
  • Datasheets with a clause-by-clause compliance statement.
  • Battery and voltage drop calculations.
  • IP address plan, VLAN and bandwidth requirements.
  • Fire alarm interface cause-and-effect matrix, coordinated with the fire alarm contractor.
  • Cybersecurity statement.
  • Samples of reader, credential, lock and exit button upon request.
  • Test procedures and test sheets, and as-built documents at handover.

1.6 Quality Assurance

  • Manufacturer: at least [5] years in access control, ISO 9001 certified.
  • Software, controllers and readers from one manufacturer or a combination supported by the software manufacturer.
  • Authorized distributor in Egypt with local spare parts stock.
  • Contractor: authorized partner with at least [3] similar projects in the last [5] years and certified engineers.

1.7 Delivery, Storage and Handling

  • Deliver equipment in original sealed packaging.
  • Store in a dry, secure place; unissued credentials stay in the Employer's custody.
  • Protect installed devices from dust and paint until handover.

1.8 Warranty

  • [24 months] from provisional acceptance, covering parts, labour and software updates.
  • Response time: critical faults [4 hours]; other faults [next working day].
  • Spare parts available in Egypt for at least [5 years].

1.9 Spare Parts and Maintenance

  • Readers: [5%] of each type, minimum one. Door controllers: one of each type.
  • Locks and exit buttons: [5%] of each type, minimum one. Power supply: one of each type.
  • Credentials: [10%] of the installed quantity, minimum [50].

PART 2 — PRODUCTS

2.1 System Description and Architecture

The system shall be distributed and IP-based. Door controllers shall hold the database locally and make access decisions without dependence on the server, which is used for administration, monitoring and reporting.

LayerComponents
ManagementServer, database, operator workstations, enrolment readers, card printer (optional)
NetworkSecurity VLAN on the building LAN, TCP/IP
FieldDoor controllers, power supplies, fire alarm interface relays
DoorReaders, locks, door contacts, exit buttons, break-glass units
Attendance and entranceTime attendance terminals, turnstiles or speed gates, visitor kiosks

Minimum system capacity: [5,000] cardholders, [64] doors, [500] access levels and [128] time schedules, expandable by licence without hardware replacement.

2.2 Management Software and Server

  1. Client/server or web-based, with at least [5] concurrent operator clients.
  2. The user interface and reports shall be available in Arabic and English.
  3. Role-based operator accounts; all operator actions logged in an audit trail.
  4. Cardholder records with photo, validity dates and CSV import.
  5. Access levels combining doors, time schedules and holidays.
  6. Real-time door status and alarms on floor plans, with priorities and acknowledgement.
  7. Remote lock/unlock of doors and lockdown of a door group or the whole site.
  8. Reports of events, access rights and alarms, with scheduled export to PDF and CSV.
  9. Online event history shall be kept for at least [12 months]. Automatic database backup shall be configured.
  10. Integration with video surveillance and HR systems via a documented API, where specified.
  11. Physical or virtual server at the manufacturer's recommended specification plus [30%], RAID 1 minimum; hot standby [optional].
  12. All clocks shall be synchronized via NTP.

2.3 Door Controllers

  1. Each controller shall support [2 or 4] doors with entry and exit readers per door.
  2. Network interface: 10/100 Mbit/s Ethernet, TCP/IP, with encrypted communication to the server (TLS 1.2 or higher, or AES 128-bit minimum).
  3. The controller shall store at least [50,000] credentials locally and make access decisions when communication with the server is lost (offline operation).
  4. Event buffer: at least [50,000] events stored during communication loss and uploaded automatically with their original time stamps when communication is restored.
  5. Anti-passback: hard, soft and timed modes, applied per area. Global anti-passback across controllers shall be supported, with defined behaviour during network loss.
  6. Interlock: configurable between two or more doors on the same or different controllers.
  7. Door forced and held-open alarms, duress PIN, card plus PIN by schedule, and extended unlock time for persons with disabilities.
  8. Reader interfaces: OSDP over RS-485 with Secure Channel, and Wiegand (26-bit, 34-bit and custom formats).
  9. Supervised inputs with end-of-line resistors (normal, alarm, open, short).
  10. Outputs: relays rated at least 2 A at 30 V DC, with suppression for inductive loads.
  11. Lockable metal enclosure with tamper switch.
  12. Firmware shall be digitally signed and upgradable remotely.
  13. Operating environment: 0 °C to +50 °C, 10% to 90% relative humidity non-condensing.

2.4 Readers

Reader typeTechnologyTypical use
Card reader13.56 MHz smart cardOffices, internal doors
Card + PIN reader13.56 MHz smart card and keypadServer rooms, cash offices
Fingerprint readerFingerprint + card + PINHigh-security rooms
Face recognition readerFace + card + PIN, with liveness detectionMain entrances, laboratories
  1. Card readers shall read 13.56 MHz smart cards to ISO/IEC 14443 Type A, using encrypted application data with mutual authentication (AES 128-bit). Systems that read only the card serial number (CSN) are not acceptable for secure areas.
  2. 125 kHz proximity technology shall not be used for new credentials because it can be copied easily. Multi-technology readers may be used only during an approved migration from existing 125 kHz cards.
  3. PIN keypads shall accept 4 to 8 digit codes; scrambled keypads for [high-security doors].
  4. Fingerprint readers: sensor resolution 500 dpi minimum, live-finger detection, capacity of at least [3,000] templates, identification time under 1 second, false acceptance rate not greater than 0.001% at the configured security level as declared by the manufacturer.
  5. Face recognition readers: visible and infrared cameras, liveness detection against photos and video, capacity of at least [10,000] faces, recognition time under 1 second, recognition distance [0.5 m to 2 m].
  6. Biometric data shall be stored as encrypted templates, not as images, and shall not be readable from the device.
  7. Reader interface: OSDP with Secure Channel is preferred. Wiegand is acceptable only where the reader cable runs inside the secured area and the reader has a tamper output.
  8. Outdoor readers: IP65 minimum per IEC 60529; readers exposed to vandalism: IK08 minimum per IEC 62262.

2.5 Credentials

  • Cards: ISO/IEC 7810 ID-1 size, printable PVC or composite, 13.56 MHz with AES-128 secured application.
  • Site-specific diversified keys shall be used and handed over to the Employer. Manufacturer default keys shall not be used.
  • Quantity: [1,000] cards and [100] key fobs. Credential numbers shall be unique and not duplicated.

2.6 Locking Hardware

  1. Electromagnetic locks: holding force at least [500 kg (approximately 1,100 lbf)] for external and main doors and [280 kg (approximately 600 lbf)] for internal doors; 12/24 V DC; built-in lock status (bond) sensor; surge suppression; no residual magnetism; mounting brackets suited to the door type.
  2. Electric strikes: field-selectable fail-safe or fail-secure, matched to the existing lock body and door weight, with monitoring of the latch.
  3. Electric mortise locks or drop bolts shall be used for glass doors and high-security doors where specified.
  4. Doors on escape routes and fire exits shall either use fail-safe locks released on power failure and fire alarm, or allow free mechanical egress at all times by panic or emergency exit hardware to EN 1125 or EN 179. Electrically controlled exit systems shall comply with EN 13637 where used. The final arrangement shall be approved by the Civil Defence authority.
  5. Fail-secure locks shall be used only where mechanical free egress from the secured side is always available.

2.7 Exit Devices, Break-Glass Units and Door Contacts

  • Exit buttons: illuminated, labelled «EXIT/خروج», stainless steel or no-touch infrared type. The exit button shall signal the controller and, for fail-safe locks, also interrupt lock power directly through its own contact.
  • Emergency break-glass units: green, resettable element (no breakable glass), test key, double-pole contacts: one pole cuts lock power directly in hardware, the second is monitored by the controller.
  • Door contacts: recessed magnetic type for timber doors, heavy-duty surface type for steel and roller doors; supervised wiring.

2.8 Power Supplies

  1. Input 220–240 V AC, 50 Hz; regulated 12 or 24 V DC output as required by the locks and controllers.
  2. Rated capacity at least 125% of the calculated load.
  3. Sealed lead-acid batteries sized for at least [4 hours] standby of controllers, readers and fail-secure locks.
  4. Individually fused outputs, a fire alarm input that removes power from fail-safe lock outputs, and monitored outputs for AC failure, low battery and tamper.
  5. Lockable metal enclosure with tamper switch; compliance with IEC 62368-1.

2.9 Fire Alarm Interface

  1. The fire alarm control panel shall provide a monitored volt-free contact per [fire zone / building / floor].
  2. On fire alarm, all fail-safe locks on escape routes in the affected [zone] shall release by direct hardware interruption of lock power. Release shall not depend on software or the network.
  3. Turnstile and speed gate barriers shall open or free-wheel on fire alarm.
  4. Doors shall re-lock only after the fire alarm panel is reset.
  5. Interface wiring between the fire alarm panel and the access control power supplies shall use fire-resistant cable tested to IEC 60331.

2.10 Time Attendance Terminals and Software

  1. Terminals shall support [face / fingerprint / card] identification, a colour display of at least [4 inches], Arabic and English interface, TCP/IP, and PoE or 12 V DC power with backup.
  2. Capacity: at least [3,000] users and [100,000] transactions stored locally, transferred automatically to the server.
  3. Terminals and access control shall share one cardholder database; duplicate data entry is not acceptable.
  4. The software shall support fixed, rotating, flexible, split and overnight shifts, configurable weekends, official holidays, Ramadan working hours, grace periods and overtime rules.
  5. Leave, permissions and missions shall be entered with an approval workflow; manual corrections shall be recorded in the audit trail.
  6. Reports: daily attendance, late arrival, early departure, absence, overtime and monthly timesheet, in Arabic and English, with export to payroll in [CSV / spreadsheet / API].

2.11 Turnstiles and Speed Gates (Optional)

  • Type: [tripod turnstile / speed gate / full-height turnstile]; number of lanes: [2] plus [1] wide lane of at least [900 mm] for wheelchairs and goods.
  • Housing: AISI 304 stainless steel minimum; indoor installation unless otherwise stated.
  • Bidirectional operation with readers on both sides; throughput of at least [30] persons per minute per lane for speed gates.
  • Infrared sensors for anti-tailgating detection and safety sensors that prevent barriers closing on a person.
  • Barriers shall open or free-wheel on power failure and on fire alarm.

2.12 Visitor Management (Optional)

  • Pre-registration by hosts and arrival notification.
  • ID scanning with the visitor's consent, and photo capture.
  • Printed visitor badges and temporary credentials (card or QR code) with automatic expiry.
  • Visitor history reports.

2.13 Cybersecurity

  1. All default passwords shall be changed. Passwords shall meet a policy of at least [12] characters with complexity and lockout after repeated failures.
  2. Communication between server, clients and controllers shall be encrypted (TLS 1.2 or higher). Card data shall be protected with AES 128-bit as a minimum.
  3. OSDP Secure Channel shall be enabled where OSDP readers are used.
  4. Unused services and ports (for example Telnet, FTP) shall be disabled.
  5. The access control network shall be on a dedicated VLAN, separated from user networks.
  6. The manufacturer shall provide security patches for at least [5] years and publish a vulnerability disclosure process.

2.14 Cables

  • Network: Category 6 U/UTP to ANSI/TIA-568.2-D.
  • OSDP: shielded twisted pair, 120 ohm, suitable for RS-485.
  • Wiegand readers: multi-core shielded cable, 0.22 mm² minimum, as recommended by the manufacturer.
  • Lock power: 2-core, minimum 1.0 mm², sized by voltage drop calculation.
  • Indoor cables: LSZH sheath tested to IEC 60332-1, IEC 61034 and IEC 60754.

PART 3 — EXECUTION

3.1 Examination

  • Inspect doors, frames, ironmongery, power points, network ports and containment.
  • Report any condition that prevents correct installation in writing before starting work.

3.2 Installation

  • Install door controllers and power supplies inside the secured area or in security/IT rooms, never on the unsecured side.
  • Mount readers at [1,000–1,200 mm] above finished floor on the lock side of the door, and exit buttons and break-glass units on the secured side, adjacent to the door.
  • Electromagnetic locks shall be mounted on the secured side of the door.
  • Bond and earth equipment in accordance with ANSI/TIA-607 and the manufacturer's instructions.

3.3 Cabling and Labelling

  • Install all cables in conduit, trunking or cable tray, separated from power cables.
  • Category 6 cabling: permanent link not exceeding 90 m and channel not exceeding 100 m.
  • Wiegand cable runs shall not exceed 150 m; OSDP runs shall be terminated with 120 ohm resistors and remain within the manufacturer's limits.
  • Voltage drop at the lock terminals shall not exceed 10% of the nominal voltage.
  • Label cables at both ends, and label controllers, power supplies and door devices in accordance with ANSI/TIA-606, using the door numbers of the approved door schedule.

3.4 Configuration and Programming

  • Configure IP addressing and VLAN according to the approved plan; synchronize time with NTP, including daylight saving changes where applicable.
  • Program access levels, time schedules and holidays according to the access matrix approved by the Employer.
  • Set door timings: unlock time [5 seconds], held-open alarm [30 seconds], extended times where required.
  • Configure anti-passback, interlocks and floor plans; enrol credentials and biometrics.
  • Create operator accounts with defined roles, change all default passwords and configure automatic backup.

3.5 Testing and Commissioning

Every controlled door shall be tested, and a signed test sheet shall be produced for each door. Tests shall be witnessed by the Engineer.

TestAcceptance criterion
Valid credentialAccess granted, door unlocks for the set time, event logged
Invalid, expired or out-of-schedule credentialAccess denied, event logged
Card + PIN, biometric, duress PINOperate as programmed; duress raises a silent alarm
Exit button and break-glass unitDoor releases; break-glass cuts lock power without the controller
Door forced and held openAlarms displayed within [2 seconds]
Tamper and supervised inputsTamper, open and short circuit reported
Mains failureFail-safe locks release; battery supports controllers for the specified time
Network disconnectionController grants and denies correctly offline; buffered events upload with correct time stamps
Anti-passback and interlockRules enforced as programmed
Fire alarm, per release groupAll doors in the group release and turnstiles open; witnessed with the fire alarm contractor
Time attendanceReports match terminal records over a [7-day] trial
CybersecurityDefault passwords changed, encryption enabled, unused services disabled

A soak period of [14 days] without critical failure is required before provisional acceptance.

3.6 Training

  • System administrators: [16 hours]; security operators: [8 hours]; HR time attendance users: [8 hours]; maintenance technicians: [8 hours].
  • On-site training in Arabic, with training material and signed attendance sheets.

3.7 Documentation and Handover

  • As-built drawings in editable CAD and PDF formats, final door schedule and IP address list.
  • Signed test sheets for every door and the commissioning report.
  • Configuration and database backups, software licences registered in the Employer's name.
  • Administrator passwords and credential site keys handed over in sealed envelopes or by another secure method.
  • O&M manuals in Arabic and English, and warranty certificates.

Related tools and products

Frequently asked questions

Why does the specification require 13.56 MHz cards instead of 125 kHz?

125 kHz proximity cards have no encryption and can be copied with low-cost devices. 13.56 MHz smart cards to ISO/IEC 14443 store AES-encrypted data with mutual authentication between card and reader, provided the system does not rely on the card serial number alone.

What happens to controlled doors on fire alarm?

Fail-safe locks on escape routes in the affected zone release by direct interruption of their power from a fire alarm panel contact, independent of software and network. Turnstiles open, doors re-lock only after the fire alarm panel is reset, and the arrangement is subject to Civil Defence approval.

What is the difference between OSDP and Wiegand reader connections?

Wiegand is a unidirectional, unencrypted interface that does not supervise the reader. OSDP is a bidirectional RS-485 protocol that continuously supervises the reader, supports encryption through Secure Channel and longer cable runs, so it is preferred, with Wiegand accepted only inside secured areas.

Can time attendance run on the same system as access control?

Yes. The specification requires one cardholder database shared by attendance terminals and door controllers, with software that handles shifts, holidays, Ramadan hours and payroll export, so data is never entered twice.

Need help designing your project?

Do Link engineers help you choose equipment and work out quantities, and they design and execute CCTV, network, intercom and access control projects, with wholesale and project prices for contractors, technicians, companies and finishing companies.