Technical Specification: Public Address and Background Music System

A vendor-neutral specification for a 100 V line public address and background music system, covering amplifiers, zoning, microphones, loudspeakers, cabling, acoustic design criteria, fire alarm interface and testing. It is written for consultants, engineers and contractors to insert into tender documents with light editing.

Vendor-neutral, no brand names. Review it against the code adopted for your project and fill in the values in [brackets].

PART 1 — GENERAL

1.1 Scope of Work

This section specifies the supply, installation, programming, testing, commissioning and handover of a complete public address (PA) and background music (BGM) system using 100 V constant-voltage loudspeaker lines for [project name / building], with [number of zones] zones covering [areas served]. The work includes:

  • Central rack equipment: mixer/pre-amplifiers, power amplifiers, zone selector or audio matrix, music sources, monitoring panel and power supply.
  • Paging microphone stations and, where specified, remote input points.
  • Ceiling, wall, column and horn loudspeakers with transformer taps, and local volume controls.
  • Cabling, containment, labelling, racks and all accessories.
  • Interface with the fire detection and alarm system.
  • Acoustic design calculations, shop drawings, testing, commissioning, training, documentation and warranty.

Where the system is also used for voice alarm (voice evacuation), the control and indicating equipment shall comply with EN 54-16, the loudspeakers with EN 54-24 and the power supply with EN 54-4, and the system shall be designed to [BS 5839-8 / NFPA 72 / the project code] and the Egyptian fire protection code. Where it is not certified for voice alarm, the PA system shall not be counted as a life-safety alarm system and the fire alarm sounders remain the primary means of warning.

1.2 Related Sections and Systems

  • Fire detection and alarm system (alarm signals per zone, evacuation and alert commands).
  • Electrical power: dedicated circuit 220–240 V AC, 50 Hz from the essential (generator-backed) supply, with UPS or batteries as specified.
  • Structured cabling and IP network (for IP-based PA, where specified).
  • Architectural ceilings and interior design (speaker positions and finishes).

1.3 Reference Standards

  • IEC 60268-16 — Sound system equipment. Objective rating of speech intelligibility by speech transmission index.
  • EN 54-16 — Voice alarm control and indicating equipment.
  • EN 54-24 — Components of voice alarm systems. Loudspeakers.
  • EN 54-4 — Power supply equipment.
  • BS 5839-8 — Code of practice for the design, installation, commissioning and maintenance of voice alarm systems.
  • NFPA 72 — National Fire Alarm and Signaling Code (emergency communications systems).
  • IEC 62368-1 — Audio/video, information and communication technology equipment. Safety requirements.
  • IEC 60529 — Degrees of protection provided by enclosures (IP code).
  • EN 50200 — Method of test for resistance to fire of unprotected small cables for use in emergency circuits.
  • IEC 60332-1, IEC 61034 and IEC 60754 — cable flame propagation, smoke density and acid gas tests.
  • IEEE 802.3af/at — Power over Ethernet; RFC 3261 — SIP (for the IP-based option).
  • ANSI/TIA-568.2-D — Balanced twisted-pair cabling (for the IP-based option).
  • The Egyptian fire protection code where the system is used for voice alarm.

1.4 Definitions

  • 100 V line: Constant-voltage distribution in which each loudspeaker has a matching transformer with selectable power taps.
  • Zone: Group of loudspeakers that receive the same programme or announcement.
  • STI: Speech transmission index, a value from 0 to 1 rating speech intelligibility (IEC 60268-16); STIPA is its simplified measurement method.
  • Headroom: Reserve amplifier power above the connected loudspeaker load.
  • VACIE: Voice alarm control and indicating equipment.

1.5 Submittals

  1. Datasheets for all equipment; EN 54-16 / EN 54-24 certificates where voice alarm is required.
  2. Shop drawings: loudspeaker layout per zone with tap settings, zone schedule, riser diagram, rack layout and single-line diagram.
  3. Calculations: loudspeaker coverage and SPL per area, predicted STI for main spaces (acoustic simulation for large or reverberant spaces), amplifier sizing with headroom, cable voltage-drop/line loss per zone and battery/UPS sizing.
  4. Priority and zoning matrix, including the fire alarm interface.
  5. Samples of ceiling and horn loudspeakers when requested.
  6. Test procedures and, at handover, test results, as-built drawings and manuals.

1.6 Quality Assurance

  • Contractor experience: at least [5] years in professional audio/PA systems and [3] similar completed projects.
  • Design and commissioning by engineers trained by the manufacturer, with calibrated sound level meter (class 1) and STI measuring equipment.
  • Manufacturer quality system certified to ISO 9001, with a local agent providing support and spare parts in Egypt.
  • Central equipment and loudspeakers shall preferably be from one manufacturer; mixed equipment shall be certified compatible for voice alarm use.

1.7 Delivery and Storage

Equipment shall be delivered in original packaging and stored in a dry, dust-free area. Loudspeakers installed before ceiling finishing shall be protected from dust and paint.

1.8 Warranty

The complete system shall be warranted for [24] months from final acceptance, covering parts and labour. Response time: [24] hours for faults affecting paging or voice alarm and [48] hours for other faults. Where the system is used for voice alarm, preventive maintenance visits shall be made every [6] months.

1.9 Spare Parts

  • [2%] of each loudspeaker type (minimum one), one spare power amplifier channel or module of the largest rating, and fuses.
  • Spare parts availability for at least [7] years.

PART 2 — PRODUCTS

2.1 System Description

  • Centralised analogue system with 100 V loudspeaker lines, or an IP-based system as described in clause 2.9 where specified.
  • Zones: [number of zones], each with independent selection for paging and BGM, and independent BGM source and volume.
  • Priority levels (highest first): emergency/voice alarm messages, live emergency microphone, general paging, pre-recorded announcements, BGM. A higher priority shall override a lower one automatically.
  • Paging shall automatically mute or reduce (duck) BGM in the selected zones and restore it after the announcement.
  • Pre-announcement chime, and storage of at least [8] pre-recorded messages in Arabic and English.
  • Expansion capacity of at least [20%] in zones and amplifier power.

2.2 Mixer / Pre-Amplifier

  1. At least [6] inputs: microphone inputs (balanced, with 48 V phantom power) and line inputs.
  2. Priority / VOX muting on at least [1] microphone input, adjustable threshold and release.
  3. Bass/treble or parametric equaliser per output, and a limiter.
  4. Frequency response at least [50 Hz – 20 kHz, ±3 dB], signal-to-noise ratio at least [80 dB], THD below [0.5%].
  5. Power supply 220–240 V AC, 50 Hz, with 24 V DC backup input where voice alarm is required.

2.3 Power Amplifiers

  1. Class D or equivalent high-efficiency amplifiers, rack-mounted, with 100 V output (70 V selectable where required) and low-impedance output.
  2. Rated output per channel: [120 / 240 / 480 W], as selected by the sizing calculation.
  3. Frequency response at least [60 Hz – 18 kHz, ±3 dB] at rated power, signal-to-noise ratio at least [90 dB], THD below [1%] at rated power.
  4. Protection against short circuit, overload, over-temperature and DC on output, with front-panel status indication.
  5. Amplifier sizing: total tap power connected to each channel shall not exceed [80%] of the rated amplifier power (minimum [20–25%] headroom), after allowing for line losses.
  6. Where voice alarm is required: standby amplifier(s) with automatic changeover on failure, monitoring of each amplifier and battery backup through EN 54-4 power supply equipment.
  7. Safety compliance with IEC 62368-1.

2.4 Zone Selector / Audio Matrix

  • [number of zones] zones with front-panel selection buttons and LED indication, and all-call function.
  • Matrix routing of any source to any zone with the priority levels defined in clause 2.1.
  • Monitored contact inputs from the fire alarm system (at least one per evacuation zone, plus "alert" and "evacuate" commands), and fault output to the fire alarm system.
  • Volume-control override: relay outputs (24 V DC) to bypass local volume controls so that announcements of priority reach every loudspeaker at full level.
  • Line monitoring of loudspeaker circuits (short, open, earth fault) where voice alarm is required, and recommended for all systems.
  • Event log and programmable schedules for BGM and announcements.

2.5 Paging Microphones

  • Desktop paging stations with gooseneck condenser or dynamic microphone, press-to-talk button, chime and zone-selection keys for [number] zones and all-call.
  • Indication of busy/occupied system and of the selected zones.
  • Connection over twisted pair or network up to [500 m] from the rack without loss of quality.
  • Emergency microphone (fireman's microphone) with highest priority, located at the fire control point, where voice alarm is required.

2.6 Music Sources

  • Media player with USB and network streaming, and FM tuner where specified.
  • Auxiliary inputs for external sources at [reception / event areas].
  • Programme selection per zone where multi-programme BGM is required.

2.7 Loudspeakers

TypeTypical useMinimum requirements
Ceiling loudspeakerOffices, corridors, lobbies, retail[6] W with taps [6 / 3 / 1.5] W at 100 V; frequency range [80 Hz – 16 kHz]; sensitivity at least [88 dB] (1 W/1 m); metal fire dome where required
Wall/cabinet loudspeakerAreas without false ceiling[6–10] W with taps; wall bracket; ABS or metal enclosure
Column loudspeakerHalls, mosques, high ceilings, reverberant spaces[20–40] W with taps; controlled vertical dispersion
Horn loudspeakerCar parks, plant rooms, outdoor areas[10–30] W with taps; IP65 or better per IEC 60529; sensitivity at least [105 dB] (1 W/1 m)
  • Every loudspeaker shall have a 100 V matching transformer with at least three power taps marked on the unit.
  • For voice alarm: loudspeakers certified to EN 54-24 with ceramic terminal block and thermal fuse so that a fire-damaged loudspeaker does not short the line.
  • Local volume controls (attenuators) shall be of the [3-wire / 4-wire] type with override relay for priority announcements.

2.8 Cables

  • Loudspeaker lines: 2-core stranded copper, minimum [1.5 mm²], sized so that line loss does not exceed [0.5 dB] at the far end of each zone.
  • Where the system is used for voice alarm: fire-resistant LSZH cable tested to EN 50200, with the fire performance required by [BS 5839-8 / the project code], red sheath, and A/B loudspeaker circuits where specified so that loss of one circuit does not silence an area.
  • For other circuits: LSZH cable complying with IEC 60332-1, IEC 61034 and IEC 60754.
  • Microphone and line-level signals: shielded twisted-pair audio cable, routed separately from mains and loudspeaker cables.

2.9 IP-Based PA (Optional)

  • Network audio endpoints (amplified speakers, decoders, paging stations) powered by PoE to IEEE 802.3af/at.
  • Audio over IP using multicast with IGMP snooping on the network switches, and QoS (DSCP marking) for audio traffic.
  • SIP (RFC 3261) registration to the telephone system for paging from telephone extensions.
  • Central management software for zones, schedules, monitoring of endpoint status and logs.
  • Cabling to ANSI/TIA-568.2-D Category 6 or higher, 90 m permanent link / 100 m channel.
  • An IP-based system may be used for voice alarm only if the complete system is certified to EN 54-16 or the project code.

PART 3 — EXECUTION

3.1 Examination and Design Criteria

  • Before installation, verify ceiling heights, room finishes, ambient noise and reverberation of main spaces against the design assumptions.
  • Loudspeaker layout shall be based on ceiling height, dispersion angle and required SPL. Ceiling loudspeakers shall be spaced so that SPL variation within an occupied area does not exceed [±3 dB] for speech.
  • Design SPL: speech at least [10 dB(A)] above the ambient noise level in each area, with a maximum of [100 dB(A)] at listener positions.
  • Intelligibility target: STI at least [0.50] in occupied areas (common target for voice alarm per IEC 60268-16 and BS 5839-8), or as specified by the Engineer.
  • Amplifier power: sum of tap settings per zone × [1.25] (headroom) plus line losses, rounded up to the next amplifier size.

3.2 Installation

  • Install equipment in a ventilated [19-inch, 42U] rack with spare rack space of [20%], cooling fans where needed, and separation between amplifiers.
  • Loudspeakers shall be fixed with brackets or safety wires independent of ceiling tiles; horn loudspeakers aimed to avoid echo from hard surfaces.
  • Voice alarm equipment shall be installed in a fire-protected room or in the fire control room as required by the project code.
  • Earthing of the rack to the building earth; no ground loops on audio signal lines.

3.3 Cabling and Labelling

  • Each zone shall have its own home-run loudspeaker line from the rack; loudspeakers connected in parallel.
  • Fire-resistant cables shall be fixed with metal clips and supports; no plastic ties as sole support.
  • Insulation resistance between conductors and to earth shall be at least [2 MΩ] before connection of equipment.
  • Cables labelled at both ends with zone number; rack terminals and loudspeakers labelled with zone and tap setting.

3.4 Configuration and Programming

  • Program zones, priorities, BGM schedules, pre-recorded messages and the fire alarm interface according to the approved matrix.
  • Recorded messages shall be prepared in Arabic and English with clear diction, and their wording approved by the client before loading.
  • Equaliser and limiter settings per zone shall be adjusted on site to improve intelligibility and avoid feedback.
  • On fire alarm signal: mute BGM in all zones, override volume controls, and broadcast alert or evacuation messages according to the cause-and-effect matrix of the fire alarm system.

3.5 Testing and Commissioning

  1. Line impedance measurement for every zone with an impedance meter and comparison with the calculated value (for 100 V lines, Z = 10,000 / P, e.g. 100 Ω for a 100 W load).
  2. Insulation resistance and earth-fault tests for every loudspeaker line.
  3. Zone tests: each zone selected individually to confirm correct speakers, no crosstalk and correct operation of all loudspeakers and volume controls.
  4. SPL measurements with a class 1 sound level meter on a grid in every area, and ambient noise measurement; results recorded against the design.
  5. STI measurements using STIPA per IEC 60268-16 in representative positions of every area or as agreed with the Engineer; areas below target shall be corrected and retested.
  6. Priority tests: emergency over paging over BGM; volume-control override; all-call.
  7. Fire alarm interface test with the fire alarm contractor for every zone input and message.
  8. For voice alarm: amplifier changeover, fault monitoring, mains failure and battery duration of [24 h standby + 30 min alarm, or as the project code requires].
  9. Final witnessed acceptance test with the Engineer.

3.6 Training

The contractor shall provide [1] day of operator training (paging, zone selection, BGM, schedules) and [2] days of technical training (settings, fault finding, monitoring), in Arabic.

3.7 Documentation and Handover

  • As-built drawings showing every loudspeaker with zone and tap setting.
  • Final calculations, programming backup and zone/priority matrix.
  • Measured impedance, SPL and STI results for every zone.
  • Operation and maintenance manuals, warranty certificate and spare parts list.

Related tools and products

Frequently asked questions

Why are 100 V lines used in public address systems?

Constant-voltage distribution allows many loudspeakers to be connected in parallel over long distances with reasonable cable sizes, with each loudspeaker's power selected from its transformer taps. This makes amplifier sizing and zoning straightforward.

Can a standard PA system be used for voice evacuation?

It should not be relied on for voice evacuation unless the control equipment complies with EN 54-16 and the loudspeakers with EN 54-24 or the project code, with fire-resistant cabling, line monitoring, standby amplifiers and battery backup.

How is the required amplifier power calculated?

Add the selected tap settings of all loudspeakers in each zone, multiply by a headroom factor of about 1.25 and allow for line losses, then select the next amplifier size so that the load does not exceed 80% of its rated power.

What STI value should the project require?

The consultant sets the target; a common value for voice alarm systems is at least 0.50, measured with the STIPA method per IEC 60268-16 during commissioning and acceptance.