Fire Alarm Battery Calculator
Enter the standby and alarm current of the panel and devices and the required standby and alarm times to see the battery capacity needed.
Battery capacity needed (BS 5839-1)
- Standby capacity0 Ah
- Alarm capacity0 Ah
- Suggested batteries (24 V panel)-
Check the maximum battery capacity the panel accepts in its datasheet.
The formula
The calculator uses the British Standard BS 5839-1 formula: capacity in Ah = 1.25 × (standby hours × standby current + 1.75 × alarm hours × alarm current). The 1.25 factor allows for battery ageing over its life, and the 1.75 factor allows for the lower capacity a battery delivers at the high discharge rate of an alarm. Common values are 24 hours standby and half an hour of alarm; some projects require longer times.
Worked example
A panel and devices drawing 0.3 A in standby and 1.5 A in alarm, with 24 hours standby and half an hour of alarm: 24 × 0.3 = 7.2 and 1.75 × 0.5 × 1.5 = 1.31, a total of 8.51, and with the 1.25 factor about 10.6 Ah, so two 12 V 12 Ah batteries fit.
Where do the currents come from?
- Panel standby and alarm current from its datasheet.
- Each detector, sounder and module current from its datasheet, multiplied by quantity.
- On addressable panels the panel software sometimes provides a ready current calculation.
The calculator helps with design; the required times are set by the code adopted for the project, the consultant and the authorities.
Related products from Do Link
Frequently asked questions
What is the fire panel battery formula?
Per BS 5839-1: capacity = 1.25 × (standby time × standby current + 1.75 × alarm time × alarm current), with times in hours and currents in amps.
Why the 1.25 and 1.75 factors?
1.25 allows for capacity loss as the battery ages, so it can still run the system near the end of its life; 1.75 allows for the lower capacity delivered at the high discharge rate of an alarm.
One battery or two?
Most fire panels run on 24 V, which means two 12 V batteries in series with the same capacity. Check the panel datasheet for the maximum capacity it accepts.
Need help designing your project?
Do Link engineers help you choose equipment and work out quantities, and they design and execute CCTV, network, intercom and access control projects, with wholesale and project prices for contractors, technicians, companies and finishing companies.