UPS Runtime Calculator

Enter the load in watts and the UPS rating and batteries to see the approximate backup time during a power cut, or the capacity needed for the time you choose.

More precise settings (optional)
0

Approximate backup time (h:mm)

  • UPS capacity in watts0 W
  • Load level0 %
  • Power drawn from the batteries0 W
  • Nominal battery energy0 Wh
  • Battery capacity for the required time0 Ah
  • Minimum suggested UPS rating0 VA

Estimates for new lead-acid batteries at 25 °C; cold and battery ageing reduce the real time.

How the calculator works

The calculator first works out the power actually drawn from the batteries: the device load divided by UPS efficiency, plus the UPS's own consumption from fans and control circuits. This fixed consumption matters with small loads, where it can be a large share of the total.

It then uses a typical discharge curve for sealed lead-acid batteries: the faster the discharge, the smaller the share of nominal energy a battery delivers before reaching its end voltage. The calculator interpolates smoothly between the points below and finds the time at which available energy equals what the load draws:

Discharge timeShare of nominal energy available
5 minutes32%
15 minutes45%
30 minutes54%
1 hour62%
3 hours76%
5 hours83%
10 hours92%
20 hours100%

These are typical values for new 12 V lead-acid batteries at 25 °C; the discharge tables in each battery datasheet give exact figures, and cold and ageing reduce the time.

VA and watts

A UPS is rated in VA, while what it can actually supply is in watts: VA multiplied by the power factor in the datasheet. The calculator checks the load in both watts and VA, and a UPS should not be loaded beyond about 80% of its rating.

Number of batteries and voltage

Each UPS runs on a set battery voltage, such as 12, 24 or 36 V. If you enter it in the more precise settings, the calculator checks that the number of batteries is a multiple of the batteries needed in series.

Worked example

A recorder, switch and cameras drawing 120 W in total, on a 1000 VA UPS with two 12 V 9 Ah batteries at 85% efficiency: the batteries supply about 161 W (141 W for the load and 20 W own consumption), nominal energy is 216 Wh, so the approximate time is about 48 minutes.

Related products from Do Link

Frequently asked questions

How long does a 1000 VA UPS run?

It depends on the load, the batteries and the UPS own consumption, not on the VA figure alone. Enter your load and the UPS batteries in the calculator to see the approximate time.

What is the difference between VA and W?

VA is apparent power and W is the real power devices use. A UPS watt rating equals its VA multiplied by the power factor in its datasheet.

Can I add batteries to increase the time?

Only on units that support external batteries, with the voltage and number set by the manufacturer. Most small UPS units have fixed internal batteries.