PART 1 — GENERAL
1.1 Scope of Work
This section covers the supply, installation, configuration, testing and commissioning of a complete IP telephony system based on the Session Initiation Protocol (SIP) for [project name], including:
- IP PBX (on-premise appliance or virtual machine) licensed for [number of extensions: 200], expandable to [500] by licence only.
- SIP trunks and/or ISDN PRI (E1) gateway for [number of channels: 30] simultaneous external calls.
- FXS gateways for [number] analog extensions and FXO gateways for [number] analog exchange lines.
- IP phones: basic [number], executive [number] and operator consoles [number].
- DECT or Wi-Fi phones [optional: number].
- Call recording, voicemail, conferencing, call detail records and reporting.
- Integration with intercom and door phones via SIP.
- Configuration of the numbering plan, call flows and security; training, documentation and warranty.
The LAN, PoE switches and structured cabling are provided under other sections unless stated otherwise; the Contractor shall define the network requirements and verify them before installation.
1.2 Related Sections and Systems
- Structured cabling system.
- Data network (LAN switches, PoE, VLANs, wireless LAN).
- UPS and electrical power.
- Intercom and door entry system; public address (paging interface, where specified).
- Services of the licensed telecom operator (SIP trunks, E1 lines, number ranges).
1.3 Reference Standards
| Standard | Title |
|---|---|
| RFC 3261 | SIP: Session Initiation Protocol |
| RFC 3264 | An Offer/Answer Model with the Session Description Protocol (SDP) |
| RFC 3550 | RTP: A Transport Protocol for Real-Time Applications |
| RFC 3711 | The Secure Real-time Transport Protocol (SRTP) |
| RFC 4733 | RTP Payload for DTMF Digits, Telephony Tones, and Telephony Signals |
| RFC 5246 / RFC 8446 | The Transport Layer Security (TLS) Protocol Version 1.2 / Version 1.3 |
| RFC 2474 / RFC 3246 | Differentiated Services Field (DS Field) / An Expedited Forwarding PHB |
| ITU-T G.711, G.722, G.729 | Speech codecs: PCM 64 kbit/s, wideband 7 kHz, CS-ACELP 8 kbit/s |
| ITU-T G.114 | One-way transmission time |
| ITU-T G.168 | Digital network echo cancellers |
| ITU-T G.703 | Physical/electrical characteristics of hierarchical digital interfaces |
| ITU-T Q.931 | ISDN user-network interface layer 3 specification for basic call control |
| ITU-T T.38 | Procedures for real-time Group 3 facsimile communication over IP networks |
| ITU-T H.264 | Advanced video coding for generic audiovisual services |
| ITU-T E.164 | The international public telecommunication numbering plan |
| IEEE 802.1Q | Bridges and Bridged Networks (VLAN tagging and priority) |
| ANSI/TIA-1057 | Link Layer Discovery Protocol for Media Endpoint Devices (LLDP-MED) |
| IEEE 802.3af/at | Power over Ethernet / Power over Ethernet Plus |
| IEEE 802.11 | Wireless LAN |
| ETSI EN 300 175 | Digital Enhanced Cordless Telecommunications (DECT); Common Interface |
| ANSI/TIA-568.2-D | Balanced Twisted-Pair Telecommunications Cabling and Components Standard |
| ANSI/TIA-606 | Administration Standard for Telecommunications Infrastructure |
| IEC 62368-1 | Audio/video, information and communication technology equipment – Part 1: Safety requirements |
The system shall also comply with the regulations of the Egyptian telecommunications regulator and the requirements of the licensed operator.
1.4 Definitions
- IP PBX: the call control server that registers extensions and routes calls.
- SIP trunk: external telephone lines delivered by the operator over IP.
- PRI / E1: digital ISDN interface with 30 voice channels.
- FXS: port that feeds an analog phone or fax. FXO: port that connects to an analog exchange line.
- IVR / auto attendant: automatic voice menu that routes callers.
- Hunt group: group of extensions that receives calls in a defined order.
- CDR: call detail record. BLF: busy lamp field key. DID: direct inward dialling number.
- QoS / DSCP: network prioritization of voice traffic using DiffServ code points.
1.5 Submittals
- System architecture drawing showing the IP PBX, gateways, trunks, network and endpoints.
- Datasheets with a clause-by-clause compliance statement.
- Draft numbering plan, class of service matrix and IVR call flow diagrams.
- Trunk dimensioning using Erlang B at a grade of service of [1%], based on [busy hour traffic].
- Bandwidth calculation per codec and PoE budget per switch.
- UPS load and autonomy calculation.
- Security hardening plan.
- Test procedures and test sheets, and as-built documents at handover.
1.6 Quality Assurance
- Manufacturer: at least [5] years in IP telephony, ISO 9001 certified.
- IP phones and gateways shall be tested by the manufacturer for interoperability with the offered IP PBX.
- Authorized distributor in Egypt with local spare parts stock.
- Contractor: authorized partner with at least [3] similar projects in the last [5] years and certified engineers.
1.7 Delivery, Storage and Handling
- Deliver equipment in original sealed packaging; store in a dry, secure place.
- Record MAC and serial numbers of all phones on delivery for provisioning and asset registers.
1.8 Warranty
- [24 months] from provisional acceptance, covering parts, labour, software updates and any support subscription required by the manufacturer.
- Response time: total system outage [4 hours]; other faults [next working day].
- Spare parts available in Egypt for at least [5 years].
1.9 Spare Parts
- IP phones: [3%] of each model, minimum one; power adapters: [5].
- One analog gateway of each type, where gateways are used.
PART 2 — PRODUCTS
2.1 System Description and Architecture
The system shall be a SIP-based IP telephony system with centralized call control. All endpoints shall register to the IP PBX over a dedicated voice VLAN. External calls shall use SIP trunks and/or E1 gateways with automatic failover between them.
| Item | Minimum capacity |
|---|---|
| Registered extensions | [200], expandable to [500] by licence |
| Concurrent calls | [60] |
| External channels | [30] (SIP and/or E1) |
| Simultaneous recordings | [all external calls] |
| Conference rooms | [3] rooms of [10] participants |
| High availability | [optional: active/standby with automatic failover] |
2.2 IP PBX
- Platform: dedicated appliance with [dual power supplies] or a virtual machine on [the Employer's virtualization platform] at the manufacturer's recommended specification.
- Signalling: SIP to RFC 3261 over UDP, TCP and TLS; SDP offer/answer to RFC 3264.
- Codecs: G.711 A-law and µ-law, G.722 wideband; G.729 [optional]; transcoding where required.
- DTMF: RFC 4733 and SIP INFO. Fax over IP: ITU-T T.38.
- Web administration over HTTPS with role-based administrator accounts and an audit log.
- Automatic provisioning of phones (configuration, firmware, directory) over HTTPS.
- Voice prompts in Arabic and English; user portal in Arabic and English.
- Licences shall be perpetual for all extensions and features listed in this specification.
The following features shall be included:
- IVR / auto attendant with multi-level menus, time conditions for working hours and holidays, and dial-by-extension.
- Hunt groups (ring all, sequential, round robin) and call queues with announcements and music on hold.
- Call transfer (attended and blind), hold, park and pickup, call forwarding, do not disturb, call waiting.
- Caller ID presentation and caller ID-based routing.
- Boss/secretary filtering, BLF and intercom/paging to phone groups.
- Voicemail with message delivery to e-mail.
- Conference bridge with PIN protection.
- Class of service and least-cost routing across trunks.
- Central phonebook and LDAP directory.
- Softphone and mobile application licences [optional: number].
2.3 SIP Trunks and E1 (PRI) Gateway
- SIP trunks shall be compatible with the licensed operator's service, with [number] channels and DID ranges as allocated.
- E1 gateway: [1] E1 port(s) with 30 B-channels each, ISDN PRI with Q.931 signalling, G.703 120 ohm interface on RJ-48 connector.
- Echo cancellation to ITU-T G.168; clock synchronization from the operator network.
- Automatic failover between SIP trunks, E1 and analog lines; overflow routing when channels are busy.
- Trunk interfaces exposed to external networks shall provide session border controller functions: topology hiding, NAT traversal, call rate limiting and access lists.
2.4 FXS and FXO Gateways
- FXS ports for analog phones, fax machines and lift emergency phones, with caller ID and message waiting indication.
- FXO ports for analog exchange lines with disconnect supervision and caller ID detection.
- Support for T.38 fax relay and G.711 pass-through.
- Surge protection on all analog ports; 19-inch rack or wall mounting; input 220–240 V AC, 50 Hz.
2.5 IP Phones
| Feature | Basic | Executive | Operator console |
|---|---|---|---|
| Display | Backlit, at least [2.3 inch] | Colour, at least [4.3 inch] | Colour, with expansion modules |
| Line keys | At least [2] | At least [6] programmable | At least [40] BLF keys or soft console |
| Ethernet | Two ports, 10/100/1000 Mbit/s | Two ports, 10/100/1000 Mbit/s | Two ports, 10/100/1000 Mbit/s |
| Headset | RJ9 | RJ9, USB or Bluetooth | RJ9 or USB |
- All phones shall be powered by PoE to IEEE 802.3af; executive phones and phones with expansion modules may use IEEE 802.3at.
- HD voice: G.722 wideband; G.711 A-law/µ-law; G.729 [optional].
- Full-duplex speakerphone with acoustic echo cancellation.
- VLAN tagging to IEEE 802.1Q, automatic voice VLAN assignment by LLDP-MED (ANSI/TIA-1057), and DSCP marking.
- SIP over TLS and SRTP media encryption; 802.1X port authentication.
- Arabic and English menus; directory lookup from the central phonebook.
- Wall-mount kit for phones in corridors, kitchens and plant rooms.
2.6 DECT and Wi-Fi Phones (Optional)
- DECT: SIP DECT base stations to ETSI EN 300 175, multi-cell with seamless handover across [coverage area], encryption enabled.
- Wi-Fi phones: IEEE 802.11ac or later, WPA2/WPA3-Enterprise and fast roaming support on the wireless LAN.
- Handset talk time at least [10 hours] and standby at least [100 hours]; ruggedized IP65 handsets for [warehouses / plant areas].
- A radio site survey is required before installation and after commissioning.
2.7 Call Recording
- Recording of all or selected extensions and trunks, with on-demand recording by users with permission.
- Retention of [12 months] on internal or network storage; encrypted storage and access logging.
- Search by date, time, extension and number; playback and download controlled by user role.
- Announcement to callers that the call may be recorded, where required.
2.8 Call Detail Records and Reports
- CDRs for every call: date, time, source, destination, trunk, duration and disposition.
- Reports by extension, department and trunk, with scheduled export to PDF and CSV.
- Call cost estimation from a tariff table entered by the Employer.
- Alerts for abnormal call patterns, such as international calls outside working hours.
2.9 Intercom and Door Phone Integration
- SIP door stations shall register as extensions on the IP PBX and call [reception / security] hunt groups.
- Video-capable phones shall display video from door stations using ITU-T H.264.
- Door opening from the phone by DTMF code or soft key, configurable per door.
- Lift emergency phones shall connect by FXS or SIP with automatic dialling to [security].
2.10 Network Requirements
- Dedicated voice VLAN (IEEE 802.1Q) with automatic assignment to phones by LLDP-MED.
- QoS: voice media marked DSCP EF (46) to RFC 3246 and signalling marked CS3 (24), with priority queuing on all switches and WAN links.
- PoE switches to IEEE 802.3af/at with a PoE budget of at least [125%] of the connected phones.
- Network targets: one-way delay not exceeding 150 ms in line with ITU-T G.114, jitter not exceeding 30 ms and packet loss not exceeding 1%.
- Bandwidth per call on Ethernet, including headers at 20 ms packetization: approximately 87 kbit/s per direction for G.711 and G.722, and approximately 31 kbit/s for G.729.
- DHCP, DNS and NTP services available on the voice VLAN.
2.11 Power and UPS
- The IP PBX, gateways, core switches and PoE switches shall be on an online double-conversion UPS with autonomy of at least [30 minutes] at full load.
- Input 220–240 V AC, 50 Hz. Equipment shall comply with IEC 62368-1.
2.12 Security
- All default passwords shall be changed. Extension SIP passwords shall be random with at least [12] characters and different from extension numbers.
- Automatic blocking of IP addresses after repeated failed registration or login attempts.
- SIP trunk access restricted to the operator's IP addresses; no open SIP ports to the internet without a session border controller.
- Administration interfaces accessible only from the management network; remote users connect through VPN or a session border controller.
- SIP over TLS 1.2 or higher (RFC 5246 / RFC 8446) and SRTP (RFC 3711) wherever endpoints support them.
- International and premium-rate calls barred by class of service and enabled only with a personal PIN.
- Unused services disabled, firmware kept updated and configuration backups encrypted.
PART 3 — EXECUTION
3.1 Examination
- Verify network readiness: voice VLAN, QoS, DHCP, PoE budget and tested cabling.
- Confirm rack space, earthing, UPS and delivery of trunks and number ranges by the operator.
- Report any deficiency to the Engineer in writing before starting work.
3.2 Installation
- Mount the IP PBX appliance and gateways in the equipment rack and earth them according to the manufacturer's instructions.
- Install phones at user locations; wall phones at [1,200–1,400 mm] above finished floor.
- Connect analog ports through the main distribution frame with surge protection.
3.3 Cabling and Labelling
- Category 6 U/UTP cabling to ANSI/TIA-568.2-D: permanent link not exceeding 90 m and channel not exceeding 100 m.
- Label patch panels, outlets and cables at both ends to ANSI/TIA-606; phones labelled with extension number.
3.4 Configuration and Numbering Plan
The numbering plan below is a typical example to be finalized with the Employer:
| Range | Use |
|---|---|
| [0] | Operator / reception |
| [100–199] | Management |
| [200–699] | General extensions by department |
| [700–749] | Hunt groups and queues |
| [750–799] | Conference rooms and voicemail |
| [800–849] | Door phones and lift phones |
| [9] + number | External line access |
- Public numbers shall follow the E.164 format on trunks.
- Emergency numbers (122 police, 123 ambulance, 180 fire) shall be dialable from every phone, with and without the external access code, and never barred.
- Classes of service: internal only, local, mobile, national and international (with PIN).
- IVR and time conditions according to the approved call flow, with working hours [Sunday–Thursday, 08:00–17:00] and official holidays.
3.5 Testing and Commissioning
| Test | Acceptance criterion |
|---|---|
| Every extension | Registers, makes and receives internal and external calls, transfer and BLF operate |
| Trunks | All channels loaded simultaneously; caller ID and DID routing correct |
| Trunk failover | Calls route to backup trunk when the primary fails |
| FXS/FXO and fax | Analog calls and T.38 fax successful |
| IVR, queues and time conditions | Every menu branch and schedule works as approved |
| Recording, voicemail, conference, CDR | Operate as specified; CDRs match test calls |
| Voice quality under load | DSCP marking verified; mean opinion score at least [4.0] for G.711 |
| Power failure | UPS supports PBX and PoE phones for the specified time |
| Emergency numbers | 122, 123 and 180 reachable from sample phones in every class of service |
| Security | Default passwords changed; failed registrations blocked; international barring effective |
| Door phone integration | Calls, video and door opening work from designated phones |
A soak period of [7 days] without critical failure is required before provisional acceptance.
3.6 Training
- System administrators: [16 hours]; operators and receptionists: [4 hours]; end users: group sessions of [1 hour].
- On-site training in Arabic, with quick reference guides in Arabic and English for each phone model.
3.7 Documentation and Handover
- As-built drawings, final numbering plan, extension list with MAC addresses and IP plan.
- Signed test sheets and commissioning report.
- Configuration backups and licences registered in the Employer's name.
- Administrator passwords handed over in sealed envelopes or by another secure method.
- O&M manuals in Arabic and English, and warranty certificates.