PART 1 — GENERAL
1.1 Scope of Work
This section covers the supply, installation, configuration, testing, commissioning and handover of a complete IP video surveillance system (IP-CCTV) for [project name and location]. The Contractor shall provide all equipment, software, licences, accessories, cabling within the scope defined below, labour and documentation required for a fully operational system.
- IP cameras: fixed bullet, dome and turret cameras, and PTZ cameras, quantity [number of cameras] as shown on the drawings.
- Network video recorders (NVRs) and/or recording servers with storage sized for [retention period: 30 days].
- PoE access switches dedicated to the CCTV network, and their connection to the building network backbone.
- Video management software (VMS), client software and mobile viewing application with all required licences.
- Monitoring workstations, monitors and, where specified, a video wall [video wall: required / not required].
- Uninterruptible power supplies (UPS) for recording, network and monitoring equipment.
- Mounting brackets, poles, junction boxes, enclosures and all installation accessories.
- Configuration, cybersecurity hardening, testing, training and as-built documentation.
1.2 Related Sections and Systems
- Structured cabling system section: horizontal copper cabling, fibre backbone, racks and labelling.
- Data network (LAN) section: core and distribution switches, routing, firewalls and backbone links.
- Electrical works: dedicated power outlets and circuits for racks, UPS and outdoor camera locations, and earthing.
- Access control, intrusion alarm and fire alarm systems where integration is required.
1.3 Reference Standards
The system shall be designed, supplied and installed in accordance with the latest editions of the following standards, in addition to applicable Egyptian codes and regulations:
- IEC 62676 series — Video surveillance systems for use in security applications, in particular IEC 62676-4 (Application guidelines).
- ONVIF Profile S, Profile G and Profile T — interoperability of IP video devices.
- IEEE 802.3af, IEEE 802.3at and IEEE 802.3bt — Power over Ethernet.
- IEEE 802.1Q — Virtual LANs; IEEE 802.1X — Port-based network access control.
- ANSI/TIA-568.2-D — Balanced twisted-pair telecommunications cabling and components.
- ISO/IEC 11801-1 — Generic cabling for customer premises.
- ANSI/TIA-606 — Administration standard for telecommunications infrastructure (labelling).
- ANSI/TIA-607 — Bonding and grounding for telecommunications.
- IEC 60332-1, IEC 61034 and IEC 60754 — Fire performance of cables: flame propagation, smoke density and halogen acid gas emission.
- IEC 60529 — Degrees of protection provided by enclosures (IP code).
- IEC 62262 — Degrees of protection against external mechanical impacts (IK code).
- IEC 62368-1 — Audio/video, information and communication technology equipment: safety requirements.
- ITU-T H.264 and ITU-T H.265 — Video coding.
- RFC 5905 — Network Time Protocol version 4 (NTP).
1.4 Definitions
- NVR: Network video recorder; a dedicated appliance that records IP camera streams.
- VMS: Video management software used to view, record, search and manage cameras.
- DORI: Detection, Observation, Recognition and Identification levels of image detail as defined in IEC 62676-4.
- Pixel density: Number of horizontal pixels per metre (px/m) at the target distance.
1.5 Submittals
- Manufacturer datasheets for every item, with compliance marked against each clause of this specification (compliance statement).
- Shop drawings: camera locations with field-of-view sketches, cable routes, rack layouts and single-line network diagram.
- Calculations: storage and retention, bandwidth per switch and uplink, PoE budget per switch, UPS autonomy, and pixel density per camera.
- Camera schedule listing each camera ID, type, lens, resolution, DORI level, mounting height, switch port and NVR channel.
- Proof of ONVIF conformance for cameras and recorders (listing on the ONVIF conformant products list).
- Testing and commissioning procedure for approval before testing starts.
- As-built drawings, configuration backups, IP address schedule and operation and maintenance manuals at handover.
1.6 Quality Assurance
- The Contractor shall have completed at least [3] IP-CCTV projects of similar size within the last [5] years and shall submit references.
- Installation and programming staff shall hold manufacturer training certificates for the offered cameras and VMS.
- Equipment shall be supplied through the manufacturer's authorised distribution channel in Egypt, with traceable serial numbers.
- The manufacturer shall have a local service partner in Egypt capable of providing warranty support and spare parts.
1.7 Delivery, Storage and Handling
- Equipment shall be delivered in original sealed packaging with labels showing model and serial number.
- Equipment shall be stored in a dry, clean and secured area protected from dust, direct sun and construction damage.
1.8 Warranty
- All equipment and installation shall be warranted for [24] months from the date of provisional acceptance.
- The Contractor shall respond to faults within [24] hours and restore service within [72] hours during the warranty period.
- Firmware and software updates released during the warranty period shall be supplied and installed free of charge.
1.9 Spare Parts and Maintenance
- The Contractor shall supply spare parts of not less than [5%] of cameras of each type (minimum one unit per type) and [1] spare hard disk per [10] installed disks.
- The Contractor shall guarantee availability of spare parts in Egypt for not less than [5] years.
PART 2 — PRODUCTS
2.1 System Description and Architecture
- The system shall be a fully IP-based, distributed architecture: cameras connect to PoE access switches, which connect over the network backbone to the recording and monitoring equipment in the [main security room / server room].
- Each camera shall stream at least two independent streams: a main stream for recording and a sub-stream for live multi-view and remote viewing.
- Recording shall be continuous 24/7 at the main stream, with event-tagged recording for analytics events [or: motion/event recording outside working hours].
- The CCTV network shall be logically separated from other networks by a dedicated VLAN, or physically separated where specified.
- The system shall support at least [20%] future expansion in cameras, recording channels, storage and switch ports without replacement of main equipment.
- All devices shall be time-synchronised from a single NTP source.
2.2 IP Cameras — General Requirements
- Image sensor: progressive scan CMOS, 1/2.8 inch or larger.
- Resolution: minimum [4 MP (2560 × 1440)] at 25 frames per second on the main stream, unless a higher resolution is required to meet the pixel density in Clause 2.3.
- Compression: H.265 and H.264, with smart/variable bitrate encoding; MJPEG for sub-stream is acceptable.
- Wide dynamic range: true WDR of at least 120 dB for cameras facing entrances, windows or strong backlight.
- Day/night: mechanical IR-cut filter with automatic switching; built-in IR illumination with a range not less than [30 m] for fixed cameras unless otherwise stated.
- Minimum illumination: 0.01 lux (colour) at F1.6 or better, and 0 lux with IR on.
- Network: 10/100 Mbps Ethernet RJ-45; IPv4 and IPv6; protocols HTTP, HTTPS, RTSP, RTP, TCP/UDP, NTP, DHCP, DNS, SNMP v3, IEEE 802.1X, QoS (DSCP), multicast.
- Interoperability: ONVIF Profile S, G and T conformance.
- Power: PoE IEEE 802.3af (Class 3 or lower) for fixed cameras; 12 V DC alternative input is preferred.
- Edge storage: microSD slot supporting at least 256 GB for recording during network loss, with automatic back-fill to the recorder where supported.
- Operating temperature: −10 °C to +60 °C as a minimum for outdoor cameras; 10–95% RH non-condensing.
- Outdoor cameras: IP67 to IEC 60529; vandal-resistant domes IK10 to IEC 62262.
2.3 Pixel Density and DORI Requirements
Each camera shall be selected (resolution and lens) to deliver at the target distance the pixel density required for its area type. Pixel density shall be calculated as horizontal resolution divided by the horizontal field-of-view width at the target distance.
| Level (IEC 62676-4) | Minimum pixel density | Typical area type |
|---|---|---|
| Detection | 25 px/m | Perimeter fences, open yards, roofs |
| Observation | 62.5 px/m | Car parks, general corridors, warehouses, open offices |
| Recognition | 125 px/m | Lobbies, lift lobbies, stair doors, shop floors |
| Identification | 250 px/m | Main entrances, reception, cash points, gates, vehicle number plates |
- The Contractor shall submit for each camera the target distance, field-of-view width and resulting pixel density.
- Number-plate capture cameras shall achieve not less than [250] px/m on the plate, with exposure set for moving vehicles at up to [30 km/h].
2.4 Fixed Cameras (Bullet, Dome and Turret)
- Lens: motorised varifocal [2.8–12 mm] with remote zoom and autofocus, or fixed lens [2.8 / 4 / 6 mm] where shown on the camera schedule.
- Bullet cameras: outdoor housing IP67, integrated sun shield, IR range not less than [50 m] for perimeter use.
- Dome cameras: vandal-resistant IK10, IP67 for outdoor or semi-outdoor use, three-axis adjustment.
- Turret cameras: IP67, three-axis adjustment, no IR reflection through a dome cover.
- Built-in analytics as defined in Clause 2.6.
2.5 PTZ Cameras
- Resolution: minimum [4 MP] at 25 fps; optical zoom not less than [25×].
- Pan 360° endless; tilt from −15° to 90° with auto-flip; pan speed at least 150°/s on preset.
- Presets: at least 300; patrol (tour) routes at least 8; pattern recording; park action and home position.
- IR range not less than [150 m] for outdoor PTZ.
- Housing: IP66 or higher to IEC 60529, IK10, with heater/fan as required for the site.
- Power: IEEE 802.3bt or the manufacturer's dedicated power supply; surge protection on power and network ports.
2.6 Video Analytics
- Cameras and/or recorders shall provide the following analytics with configurable zones, direction and schedules: line crossing (tripwire), intrusion (area entry), region entering and exiting.
- Human and vehicle classification shall be used to filter analytics alarms, so that false alarms from animals, leaves, rain and lighting changes are reduced.
- Analytics events shall trigger recording, pop-up on the client, notification to the mobile application and, where required, an output relay or a strobe/voice warning.
- Optional analytics [face detection, number plate recognition, people counting, loitering] shall be provided where listed in the camera schedule.
2.7 Network Video Recorders (NVR)
- Recording channels: [32 / 64] IP channels per NVR, with at least 20% spare channels after allocation.
- Incoming bandwidth: not less than [320 Mbps] recording throughput; outgoing bandwidth not less than [256 Mbps].
- Decoding: H.265/H.264 up to 8 MP; minimum [16] channels at 1080p live decoding for local display.
- Storage: minimum [8] SATA bays, each supporting HDDs of at least 16 TB; surveillance-grade drives rated for 24/7 operation.
- RAID 5, RAID 6 and RAID 10 support with hot spare; disk health monitoring (S.M.A.R.T.) and alarm on failure.
- N+1 recorder redundancy where specified [required / not required].
- Interfaces: at least two Gigabit Ethernet ports; HDMI output with 4K resolution; USB for export; alarm inputs/outputs.
- ONVIF Profile S, G and T compliance for third-party camera support.
- Power supply: 220–240 V AC, 50 Hz; redundant power supply for NVRs of 32 channels and above.
2.8 Storage and Retention Calculation
- Storage shall be sized for [retention period: 30 days] continuous recording of all cameras at the main stream at 25 fps, plus [20%] free space margin, after RAID overhead.
- Storage per camera (TB) = average bitrate (Mbps) × 86,400 × retention days ÷ 8 ÷ 1,000,000.
- Example: a camera averaging 4 Mbps for 30 days requires 4 × 86,400 × 30 ÷ 8 ÷ 1,000,000 ≈ 1.3 TB.
- The Contractor shall base the calculation on the manufacturer's published bitrate for the selected resolution, codec and scene complexity, and shall verify it on site during commissioning (Clause 3.5).
2.9 PoE Access Switches for CCTV
Backbone, core and distribution switching shall comply with the data network section. CCTV access switches shall meet the following minimum requirements:
- Managed Layer 2 (Layer 2+ preferred), with [8 / 16 / 24] PoE ports of 10/100/1000 Mbps and at least two 1 Gbps SFP uplink ports (10 Gbps SFP+ for aggregation switches).
- PoE: IEEE 802.3af/at on all access ports; IEEE 802.3bt on ports feeding PTZ cameras where required.
- PoE budget: not less than the sum of the maximum power of connected cameras plus 30% margin.
- Features: VLAN (IEEE 802.1Q), IGMP snooping, QoS, LACP, RSTP/MSTP, port security, IEEE 802.1X, SNMP v3, SSH, HTTPS, syslog and NTP client.
- Outdoor switches shall be industrial-grade (−40 °C to +75 °C) installed in IP66 enclosures with surge protection.
- Uplink bandwidth shall not exceed 70% utilisation under full recording and live viewing load.
2.10 Video Management Software (VMS) and Client
- Licences for [number of cameras] plus [20%] spare, with no annual subscription unless stated by the Employer.
- Live view with layouts up to 64 tiles per monitor, multi-monitor support, digital zoom, PTZ control and preset recall.
- Playback with synchronised multi-camera playback up to 16 cameras, timeline with events, fast forward/reverse and frame-by-frame.
- Export of video clips in a standard format with an included player and digital signature/watermark for evidence integrity.
- Health monitoring: camera offline, recording failure, disk failure, and network loss alarms, with email notification.
- User management with roles and per-camera rights (see Clause 2.13); audit trail of all operator actions.
- Arabic and English user interface.
- Mobile application for Android and iOS with live view, playback and push notifications, via a secure connection.
2.11 Monitoring Workstation and Video Wall
- Workstation: current-generation multi-core processor, minimum 16 GB RAM, SSD of 512 GB, dedicated graphics card capable of decoding the required number of streams, two Gigabit network ports, licensed operating system.
- Monitors: [27-inch] professional monitors rated for 24/7 operation, Full HD or higher.
- Video wall (optional): [2 × 2] array of [55-inch] narrow-bezel displays rated for 24/7 operation, total bezel gap not exceeding [3.5 mm], driven by a video wall controller or decoder, with layouts switchable from the VMS.
2.12 Cabling
- Horizontal cabling shall be Category 6 U/UTP or better, LSZH sheathed (IEC 60332-1, IEC 61034, IEC 60754), complying with the structured cabling section.
- Permanent link length shall not exceed 90 m, and channel length 100 m. Longer runs shall use fibre with media converters or remote switches.
2.13 Cybersecurity Requirements
- No device shall operate with a default password. Passwords shall be at least 8 characters combining upper and lower case letters, numbers and symbols.
- Account lock-out after [5] failed login attempts; automatic session timeout.
- User levels: administrator, supervisor, operator and viewer as a minimum, with rights per camera and per function (live, playback, export, PTZ, configuration).
- Encrypted management: HTTPS with TLS 1.2 or higher; Telnet, plain FTP and unused services disabled; SSH only where needed.
- Firmware shall be the latest stable version at handover, digitally signed by the manufacturer; the manufacturer shall publish security advisories and patches.
- CCTV devices shall be in a dedicated VLAN; access to recorders from other VLANs only through firewall rules.
- Peer-to-peer cloud services and UPnP shall be disabled unless approved by the Employer; remote access shall be through VPN or a secure gateway.
2.14 UPS for CCTV Equipment
- Online double-conversion UPS, 220–240 V AC 50 Hz input and output, pure sine wave.
- Capacity: total connected load plus [25%] margin, including PoE switches feeding cameras.
- Autonomy: not less than [30 minutes] at full load, or as required to cover changeover to the standby generator.
2.15 Time Synchronisation
- All cameras, recorders, servers, switches and workstations shall synchronise to an NTP server [on the network / provided under this section].
- Time deviation between any two devices shall not exceed 1 second.
PART 3 — EXECUTION
3.1 Examination
- The Contractor shall survey the site, verify camera locations, mounting surfaces, lighting conditions and cable routes, and report discrepancies before installation.
3.2 Installation
- Cameras shall be installed at the heights and angles in the approved shop drawings, typically 2.7–4 m for indoor and 4–6 m for outdoor fixed cameras.
- Cameras shall avoid direct sunlight, bright lights and reflective surfaces in the field of view.
- Outdoor connections shall be made in IP66 junction boxes; cable entries shall be sealed.
- Surge protectors shall be installed for cameras on poles and on building facades exposed to lightning, bonded to earth per ANSI/TIA-607.
3.3 Cabling and Labelling
- Every cable shall be labelled at both ends; every camera shall carry a label showing its ID, according to ANSI/TIA-606.
- Patch panels, switch ports and NVR channels shall be labelled to match the camera schedule.
- Every copper link shall be certified with a cable analyser to the relevant category of ANSI/TIA-568.2-D.
3.4 Configuration and Programming
- Assign static IP addresses according to an approved IP address schedule.
- Configure resolution, frame rate, bitrate and codec per camera to meet the camera schedule and storage calculation.
- Configure analytics zones, schedules and notifications in coordination with the security team.
- Apply all cybersecurity settings in Clause 2.13 and create user accounts per the Employer's list.
- Back up all configurations and hand them over on removable media.
3.5 Testing and Commissioning
Testing shall follow the approved procedure in the presence of the Engineer, and results shall be recorded on signed test sheets.
| Test | Acceptance criterion |
|---|---|
| Day image test per camera | Field of view matches the shop drawing; required DORI level achieved, verified with a test target or person at the target distance |
| Night image test per camera | Usable image with IR or available light; required level achieved for Recognition and Identification cameras |
| Recording test | All cameras recording continuously at the configured resolution and frame rate; no lost frames over 24 hours |
| Retention verification | Measured 24-hour storage consumption extrapolated to the retention period is within usable capacity with at least 20% margin; retention confirmed after the defined period before final acceptance |
| Failover tests | Removing one disk does not interrupt recording and RAID rebuilds; NVR failover (if specified) takes over recording; UPS carries the load for the specified autonomy; camera edge recording back-fills after network loss |
| Analytics test | Line crossing and intrusion events detected for persons and vehicles; no alarms from non-target objects during the test period |
| PTZ test | All presets, tours and control functions operate from the VMS |
| Cybersecurity check | No default passwords; HTTPS enabled; unused services disabled; VLAN isolation verified |
| Time sync check | All devices within 1 second of the NTP source |
| Export test | Exported clip plays on a separate PC with watermark verification |
3.6 Training
- Operator training: [2] days covering live view, playback, search, export and alarm handling, for up to [6] persons.
- Administrator training: [2] days covering configuration, users, backups, disk replacement and troubleshooting.
- Training materials shall be provided in Arabic and English.
3.7 Documentation and Handover
- As-built drawings in native CAD format and PDF.
- Final camera schedule, IP address schedule, switch port map and rack layouts.
- Configuration backups, licence certificates and administrator passwords in a sealed envelope.
- Signed test sheets, storage calculation and commissioning report.
- Operation and maintenance manuals, warranty certificates and contact list for support.