Previous
Next
Delta CL1000RT Online Crystal Series Rack-Tower UPS 1000 VA
Delta CL1000RT Online Crystal Series Rack-Tower UPS 1000 VA is a UPS product. Review its technical specifications and product data to select the right solution from Do Link Egypt.
UPS سلسلة Crystal RT من Delta، Online Double Conversion بيتركب راك أو تاور، بموجة جيبية نقية ومعامل قدرة 0.9 للسيرفرات ورواكات الشبكات.
- Online Double Conversion بموجة جيبية نقية
- تركيب راك أو تاور، وشاشة LCD بتلف
- معامل قدرة خرج 0.9 ووضع كفاءة عالية
- لحد 4 وحدات بطاريات خارجية لزمن تشغيل أطول
- اتصال RS232 و USB وكارت Relay أو SNMP
General
| Model | CL1000RT |
|---|
Key Features
- Online double conversion with pure sine wave output
- Rack / tower convertible with rotatable LCD
- Output power factor 0.9 and selectable high-efficiency mode
- Up to four external battery packs (EBPs) for longer runtime
- RS232, USB, relay or SNMP card communication
- Emergency power off (EPO) and cold start
Best Fit Applications
Server rooms, network racks, CCTV control rooms, banks and offices.
Technical Specifications
| Model | CL1000RT |
| General | |
| Topology | Online double conversion, rack / tower convertible |
| Capacity | 1000 VA / 900 W |
| Phase | Single phase with ground |
| Input | |
| Nominal Voltage | 200 / 208 / 220 / 230 / 240 VAC |
| Input Voltage Range | 110 - 300 VAC @ 60% load, 160 - 300 VAC @ 100% load |
| Frequency Range | 45 - 55 Hz / 55 - 65 Hz (auto detect) |
| Power Factor | ≥ 0.99 (100% load) |
| Output | |
| Output Voltage | 200 / 208 / 220 / 230 / 240 VAC |
| Power Factor | 0.9 |
| Voltage Regulation | ±1% |
| Frequency (Battery Mode) | 50 / 60 Hz ± 0.1 Hz |
| Crest Ratio | 3:1 |
| Harmonic Distortion | ≤ 3% THD (linear), ≤ 6% THD (non-linear) |
| Transfer Time | AC to DC: zero, inverter to bypass: 4 ms |
| Waveform | Pure sine wave |
| Efficiency | |
| AC Mode | 88% |
| Battery Mode | 83% |
| Battery | |
| Battery Type & Number | 2 / 3 × 12V 9Ah |
| Charging Voltage | 27.4 / 41.1 VDC ±1% |
| Typical Recharge Time | 4 hours to 90% capacity |
| Backup Time | Estimated remaining time on the LCD |
| Indicators & Alarms | |
| LCD | Load level, battery level, AC / battery / bypass mode, fault |
| Management | |
| Communication | Smart RS232 / USB, optional SNMP card |
| Environment | |
| Humidity | 20 - 90% RH @ 0 - 40 °C (non-condensing) |
| Noise Level | < 50 dB @ 1 m |
| Physical | |
| Dimensions D × W × H | 430 × 440 × 86.5 mm |
| Net Weight | 13.9 / 16.4 kg |
Need help choosing?
Want to learn more?