Previous
Next
Delta DS Plus 310 – 10kVA / 10kW Three-Phase Online UPS
Delta DS Plus 310 – 10kVA / 10kW Three-Phase Online UPS (DELTA-DSPLUS-310-10KVA) is a UPS product. Review its technical specifications and product data to select the right solution from Do Link Egypt.
Delta DS Plus 310 10 kVA / 10 kW three-phase online double-conversion UPS, output power factor 1.0, DSP control, ECO mode up to 98%, parallel up to 3 units, LCD touch screen.
- 10 kVA / 10 kW, output power factor 1.0
- Online double conversion with DSP control
- Efficiency up to 95%, ECO mode 98%
- Parallel up to 3 units with common battery
- LCD touch screen, EPO, generator compatible, 3/3 - 3/1 - 1/1 adjustable
General
| Model | DELTA-DSPLUS-310-10KVA |
|---|
Key Features
- 10 kVA / 10 kW, output power factor 1.0
- Online double conversion with DSP control
- Efficiency up to 95%, ECO mode 98%
- Parallel up to 3 units with common battery
- LCD touch screen, EPO, generator compatible, 3/3 - 3/1 - 1/1 adjustable
Best Fit Applications
Data centers, server rooms, hospitals, factories, banks, telecom and CCTV / security systems needing clean three-phase backup power.
Technical Specifications
| Brand | Delta (Delta Electronix) |
|---|---|
| Model | DS Plus 310 |
| Capacity | 10 kVA / 10 kW (PF 1.0) |
| Topology | Online double conversion, DSP controlled |
| Nominal Voltage | 380/400/415 V, 3Ph+N+PE (220/230 V 1Ph adjustable) |
| Operating Voltage Range | 110-300 Vac at 50% load, 175-276 Vac at full load |
| Frequency Range | 40-70 Hz |
| Input Power Factor | > 0.99 at 100% load |
| THDi | < 3% (100% linear load) |
| Generator Input | Supported |
| Output Voltage | 380/400/415 Vac, 3Ph+N+PE (220/230 V 1Ph adjustable) |
| Voltage Regulation | ±1% typical balanced load, ±2% unbalanced load |
| Output Power Factor | 1.0 |
| Crest Factor | 3:1 |
| THDv | ≤ 2% linear load, ≤ 4% non-linear load |
| Overload | 110% 1 h, 111-125% 10 min, 126-150% 1 min, > 150% 200 ms |
| Bypass Voltage Range | -30% ~ +20%, 46-54 Hz or 56-64 Hz |
| Efficiency (AC / ECO / Battery) | 95% / 98% / 94% |
| Battery Voltage | ±120 V |
| Float Charge Voltage | 2.28 V/cell (2.25-2.33 selectable), temperature compensated |
| Transfer Time | 0 ms (utility to battery and to bypass) |
| Parallel Operation | Up to 3 units (common battery supported) |
| Display | LCD touch screen |
| Communication | USB, RS485, parallel port, dry contact, intelligent slot, SNMP card (option), relay card (option) |
| Protection | Short circuit, overload, over temperature, battery low, fan fault, back-feed protection, EPO |
| Operating Temperature | 0-40 °C |
| Humidity | 0-95% non-condensing |
| Protection Class | IP20 |
| Dimensions | 630 x 250 x 830 mm (D x W x H) |
| Net Weight | 37 kg |
| Standards | IEC/EN 62040-1, IEC/EN 62040-2 Category C3 |